Filter Fan Unit PIFF COMPACT manufactured by Exyte is a Plenum Integrated unit for recirculation air handling. The integrated unit eliminates the needs of return or supply air ducts, which reduces installation costs and saves space. Cleanroom classes 5.0 to 8.0 in accordance with DIN EN ISO 14644-1, B, C and D in accordance with EC Guide "GMP" can be achieved. The unit is installed into the existing ceiling grid by an installation frame.
Specification
Grid size: length: 1,200 mm | width: 1,200 mm Housing length: 1,100 mm Housing width: 1,100 mm Housing height: 590 mm Weight: 70 kg Voltage: between 200 V and 277 V Phase: 1 ~ Frequency: 50 Hz / 60 Hz Rated current: between 1.8 A and 1.3 A Air volume flow: 1,500 m³/h Rated capacity: 280 W Sound power level: 68 dB (A) Clean room sound pressure level: 25 % occupancy: 68 dB (A) Separation efficiency in MPPS: 100 % Pressure drop: 126 Pa Cooling capacity: 2.6 kW Media volume flow: 0.4 m³/h Water temperature inlet: 14 °C Water temperature outlet: 20 °C Pressure drop: waterside: 12.7 kPa Air temperature inlet: 23 °C Air temperature outlet: 18 °C Pressure drop: airside: 42 Pa
Accessories Ceiling installation adapter for third party ceiling systems Connection pieces Prefilter Aerosol inlet-/measurement connector
Features
Energy efficiency Easy operation, low operating costs Low maintenance costs Low noise due to optimized airflow and acoustic design Easy installation with plug & play unit, ceiling installation frames and intermediate profiles Integrated air cooling coil (without valve or thermostat, water connection 3/4” female thread) Compact recirculating air cooling device Self-contained return air unit Integrated prefilter Integrated plenum Easy retrofitting (increase of the recirculating air volume or cleanroom class) No mixture of recirculation air from different production rooms Less energy consumption than traditional units. Optional makeup air and exhaust air connection Cleanroom classes 5 to 8 in accordance with ISO 14644-1 Cleanroom classes D, C, B in accordance with EU Good Manufacturing Practice guideline Particle and differential pressure measurements available at the HEPA filter Flexible in that way that the unit can be easily relocate